Alarm Lock NETWORXPANEL Especificaciones Pagina 4

  • Descarga
  • Añadir a mis manuales
  • Imprimir
  • Pagina
    / 12
  • Tabla de contenidos
  • MARCADORES
  • Valorado. / 5. Basado en revisión del cliente
Vista de pagina 3
4
steel-reinforced concrete or metal lath and plaster can
reduce NETWORXPANEL transmitter strength as much
as 90%.
Note: In difficult installations wherein distant Gateways
pose reception problems, the use of multiple Gateways
throughout the premises is recommended.
Wire Gauges
Locate the NETWORXPANEL in an easily accessible
location for servicing, within 200 feet of the keypads and/
or Wiegand devices. Standard 22-24 gauge wire is rec-
ommended for all connections between the NETWORX-
PANEL panel and the keypads/devices, and 18 gauge
wire for all magnetic locks and electric door strikes (no
more than 25 feet in length). Avoid running wires paral-
lel to other types of wiring that can cause electrical inter-
ference.
Air Circulation
Important Note: The NETWORXPANEL is powered by
a linear power supply which is the preferred power sup-
ply for card proximity readers due to their very low elec-
trical noise (compared with switching power supplies).
However, be aware that linear power supplies do gener-
ate moderate heat. Therefore mount the NETWORX-
PANEL in a location that provides air circulation around
the unit, particularly directly above the housing. Do not
install the NETWORXPANEL in confined locations.
Note: For UL installations, the NETWORXPANEL must
be mounted within a protected premises.
Fire Alarm System Integration
Before installing the Networx system, be sure to consult
with the authority having jurisdiction to be sure to comply
with all local codes. NFPA requires that the Fire Alarm
System has some control over exit doors. In the event
of a fire alarm or the loss of primary power (typically AC),
all exit doors must be unlocked. Typically, the output(s)
from the fire alarm system are wired such that if there is
a fire alarm or AC failure of the fire alarm system, the
positive (+) voltage wire of the magnetic lock is inter-
rupted, releasing the magnetic lock to allow egress. An
emergency exit button mounted next to the door can
also be used; this normally closed switch is wired in se-
ries to the positive (+) voltage wire of the magnetic lock
so that when pressed, power is cut (interrupted) to the
magnetic lock, allowing egress. NEVER use the "(T26-
T27) REMOTE RELEASE INPUT" terminals for emer-
gency exit wiring. Conform to the wiring examples
shown further in this manual.
TYPICAL INSTALLATIONS
There are several ways the NETWORXPANEL may be
installed to provide access control. Before installing any-
thing, be absolutely clear as to how the components will
be installed, wired and how the NETWORXPANEL will
be programmed. Listed below are some typical installa-
tions:
One Keypad only. One of the simplest configura-
tions is a single keypad or Wiegand device located
outside the restricted area to allow passage through a
controlled door in one direction only. This method
uses the Main Relay to unlock the controlled door,
leaving the Aux Relay unused or programmed for one
of many other purposes (such as triggering a video
camera to record the passage, or to trigger a bell lo-
cated in another room).
One Keypad and One "Remote Release" Button.
With this configuration, a single keypad or Wiegand
device is located outside the restricted area and a re-
mote release button is placed within the restricted
area. This method only requires a single keypad or
Wiegand device for the controlled door. This method
is limited in that the credential is identified in the log
only for entry via the keypad, not for exit (the use of
the remote release button is entered in the log but the
identification of the person(s) exiting is not).
Two Wiegand Devices controlling one door: Uses
two Wiegand devices, one mounted inside and the
other outside the restricted area. This configuration
requires a User Code and/or proximity credential for
both entry and exit from the restricted area. Each
credential is logged with a specific Wiegand device
identified, thus the credential used to enter or exit the
restricted area can easily be determined.
Two Networx
Keypads controlling one door:
Uses two of any combination keypad models, one
mounted inside and the other outside the restricted
area. This configuration requires a User Code (and/
or proximity credential with the NETPDK integral
proximity reader) for both entry and exit from the re-
stricted area. Each credential is logged with a spe-
cific keypad identified ("primary" or "secondary"), thus
the credential used to enter or exit the restricted area
can easily be determined.
"Two Door Mode": Two Networx
keypads (and/or
two Wiegand devices) can be used to separately con-
trol two doors. With Two Door Mode, one keypad is
designated as the "primary" keypad controlling the
Main Relay (thus a primary door), and the other as
the "secondary" keypad controlling the Aux Relay
(thus a secondary door). To control passage through
only one door, a specific User Code can be enabled
for use with only one of the two keypads, therefore
allowing control of only one of the two doors.
Although the physical wiring for Two Door Mode is
just as easy as any other type of configuration, both
keypads must wired to the same NETWORXPANEL
terminals; therefore one keypad must be designated
as "primary" and the other as "secondary". In addi-
tion, the Two Door Mode feature must be pro-
grammed (see WI1855 and program Function 67
(Feature 13, "Create Two Door Mode"). These extra
steps are incorporated in the "FIRST TIME POWER
UP" procedure, so installing a two-door configuration
will be just as easy as any other type of configuration.
Vista de pagina 3
1 2 3 4 5 6 7 8 9 10 11 12

Comentarios a estos manuales

Sin comentarios