XARTU/5™ Manual Copyright© 2013
Eagle Research Corporation
®
REV 11.1.11 Page | 21
OPTIONAL RELAY CARD (EBM80/RC4)
The optional mechanical relay card has four channels for generating pulse outputs. The
outputs are fused at 5 amps, and an individual LED provides the status of each output.
Jumper JP1 determines whether the +12 VDC power source for the relay coil is internal
or external. The default setting sources the relay coil externally. Jumpers JP2, JP3,
JP4, and JP5, one for each relay, determine whether the relay coils are energized on a
low or high logic state from the RTU. The default setting is for low logic state. Ports
P4.0, P5.0, P6.0, and P7.0 determine the addressing of the relay outputs in sets of four.
For proper function, both hardware and software addressing must match. The table
below lists the specifications for the mechanical relay card.
Electrical Isolation
Dielectric Strength
Surge Strength
750 VAC (between open contacts)
2000 VAC (between coil and contacts)
4000 V standard, 6000 V high (at 1.2x50us standard surge
wave)
Output (Switching)
Voltage
30 VDC / 250 VAC, Resistive
Output Current (max)
Momentary
Continuous
NOTE
Four of the digital I/O lines must be sacrificed to use the mechanical relay card.